Pressure Reduction Valve

The Pressure Reduction Valve is an automation symbol for a pressure reduction valve: a self-acting valve that keeps the pressure downstream of it at a set value. It is found in the Automation - OpenBridge section of the Perspective Component Palette as Valve - Pressure Reduction, next to the Valve.

It is meant to be placed in a mimic or diagram, typically in a coordinate container, on the pipe it sits in. The valve acts on its own, so there is nothing to bind: set its flow direction and tag, and place it on the line. The handle and the self-actuation line show that the medium operates it.

Pressure Reduction Valve with a tag

The Pressure Reduction Valve is one of the automation buttons. The readout and tag, the alert frame, the progress ring, the badges, the size and the positioning are shared by all of them and are described in Automation Buttons — Common Features. This page covers what is specific to the Pressure Reduction Valve.

A Pressure Reduction Valve dropped from the palette with default properties:

Pressure Reduction Valve with default properties

The valve acts on its own, so it has no open or closed state and no status row: the readout shows the tag only. flowDirection turns the symbol so the medium flows right, left, up or down; variant draws it on a round button (regular) or as the bare icon (flat) for a valve that is part of a pipe.

right left up down
regular regular, right regular, left regular, up regular, down
flat flat, right flat, left flat, up flat, down

With static set to true, the valve is drawn in the static colour, for a valve the control system does not report on:

Static valve


The handle is drawn on the side away from the readout and turns with the flow; a thin self-actuation line runs from it to the pipe, the P&ID sign for a valve that is operated by the medium itself. invertHandlePosition puts the handle on the other side, and handleSize set to small draws it from the centre of the symbol, for a flat valve without a button:

invertHandlePosition handleSize = small, flat
Handle on the other side Small handle on a flat valve

Name Description Property Type
flowDirection Direction the medium flows: auto, up, down, left or right. Default auto, which draws the flow to the right. value
variant regular draws the icon on a button, flat draws only the icon. Default regular. value
invertHandlePosition Put the handle on the other side of the valve. Default false. value
handleSize regular, or small to draw the handle from the symbol’s centre. Default regular. value
style Standard Perspective style object. object

The Pressure Reduction Valve is an automation button. The properties below work in the same way on every automation button, and are described in Automation Buttons — Common Features:

  • Readout — The tag name next to the symbol; the valve has no status row. Properties: showReadoutStack, readoutPosition, readoutSize, showStatus, showStatusIcon, hasTag, tag.
  • Positioning — Which part of the button is aligned to the component’s box. Properties: positioning.
  • Size — Size of the whole component. Properties: componentSize.
  • Activated — Highlighted background that marks the symbol as selected. Properties: activated.
  • Static — Grey symbol for a device whose state is unknown. Properties: static.
  • Alert Frame — Alert frame around the symbol. Properties: alert, alertFrameType, alertFrameStatus, alertFrameMode, alertFrameThickness, showAlertCategoryIcon, showAlertIcon, alertIcon, alertLabel, alertTimer.
  • Progress — Progress ring while a command is carried out. Properties: progress, progressMode, progressValue.
  • Badges — Badges in the corners of the symbol. Properties: badgeControl, badgeAlert, badgeInterlock, badgeCommandLocked.
  • Style — Standard Perspective style object.

The Pressure Reduction Valve has no component events of its own. The standard Perspective events, such as onClick, are available in the component’s event configuration.

Example 1 — Pressure Reduction Valve in a Pipe

Section titled “Example 1 — Pressure Reduction Valve in a Pipe”
  1. Drop a Pressure Reduction Valve into a coordinate container, on the pipe.
  2. Set variant to flat and flowDirection to the direction of the pipe.
  3. Set hasTag to true and tag to the valve’s tag, for example V-204.